Type a value in either box to convert between pascals (Pa) and inches of water column (in WC). One inch of water column is 249.0889 Pa, so -0.02 in WC is about -4.98 Pa.
Type in either box; the other one follows. A minus sign means negative pressure (the space is lower than the reference side).
Result
-4.98 Pa
| Where | Target | In pascals | Source |
|---|---|---|---|
| Negative pressure enclosure for asbestos work | At least -0.02 in WC, relative to outside the enclosure | -4.98 Pa | OSHA 29 CFR 1926.1101(g)(5)(i)(A)(3), which also calls for at least 4 air changes per hour in the enclosure |
| Temporary negative pressure isolation room | About -0.01 in WC (negative 2.5 Pa) | -2.49 Pa | Minnesota Department of Health, Airborne Infectious Disease Management: Methods for Temporary Negative Pressure Isolation |
| Protective environment room (positive pressure) | At least 0.01 in WC (2.5 Pa) | 2.49 Pa | CDC Guidelines for Environmental Infection Control in Health-Care Facilities, Appendix B |
| Pascals | in WC | in WC | Pascals |
|---|---|---|---|
| 1 Pa | 0.0040 | 0.005 in | 1.25 |
| 2 Pa | 0.0080 | 0.01 in | 2.49 |
| 2.5 Pa | 0.0100 | 0.02 in | 4.98 |
| 5 Pa | 0.0201 | 0.03 in | 7.47 |
| 10 Pa | 0.0401 | 0.04 in | 9.96 |
| 12.5 Pa | 0.0502 | 0.05 in | 12.45 |
| 25 Pa | 0.1004 | 0.1 in | 24.91 |
| 50 Pa | 0.2007 | 0.25 in | 62.27 |
| 100 Pa | 0.4015 | 1 in | 249.09 |
An inch of water column is the pressure of a column of water one inch tall. NIST lists the conventional inch of water as 249.0889 pascals, the factor used here.
Pa = in WC × 249.0889
in WC = Pa ÷ 249.0889
mm WC = Pa ÷ 9.80665
Example: OSHA's minimum of -0.02 in WC for an asbestos enclosure is -0.02 × 249.0889 = -4.98 Pa. A pressure monitor that reads ±25 Pa covers about ±0.10 in WC.
NIST Special Publication 811, Appendix B.9: inch of water, conventional = 249.0889 Pa; centimeter of water, conventional = 98.0665 Pa. OSHA, 29 CFR 1926.1101(g)(5)(i)(A). Minnesota Department of Health, Airborne Infectious Disease Management: Methods for Temporary Negative Pressure Isolation. CDC, Guidelines for Environmental Infection Control in Health-Care Facilities, Appendix B.
$1,210.00
Shows in WC or Pa from -0.10 to +0.10 in WC, with color and audible alarms.
View product : Abatement Technologies Single Room Pressure Monitor RPM-RT1$1,400.00
Portable differential pressure monitor, -25 to +25 Pa, color touch screen.
View product : Abatement Technologies Portable Differential Pressure Monitor PPM3-S$1,070.00
Negative air machine rated 2,000 CFM on high.
View product : Abatement Technologies HEPA-AIRE Series Negative Air Machine H2KM$1,070.00
Variable 200 to 750 CFM at 35 lb with filters.
View product : Abatement Technologies PREDATOR Series Portable Air Scrubber PRED750249.0889 Pa, using NIST's conventional inch of water. For quick math, 1 in WC is about 249 Pa and 1 Pa is about 0.004 in WC.
About -4.98 Pa. It is the minimum pressure differential OSHA requires inside a negative pressure enclosure for asbestos work, measured against the pressure outside the enclosure.
Yes. Inches of water column, in WC, in H2O and in w.g. (water gauge) all name the same unit.
The space being measured is at a lower pressure than the reference side, usually the hallway or room outside. That negative reading is what makes air flow in through gaps rather than out.
CFM and the number of air scrubbers for a room.